Fire Alarm Control Panel

4 zones Conventional Fire Alarm Control Panel

SPECIFICATIONS
*AC POWER
– 90~270 VAC, 50 Hz, 2.0 amps.
– Wire size: minimum 14 AWG (2.0 mm²) with 600-volt insulation.
* BATTERY
– Sealed lead-acid batteries only.
– Maximum charging circuit: 27.6VDC@ 0.8 amp for
normal flat charge.
– Maximum battery charger capacity: 18AH battery.
NOTE: two 4AH batteries can be housed in the cabinet. Larger
batteries require a separate battery box.
*Total 24 V system power: 3.0 amps.
* Notification appliance (signal) power: 2.5 amps.
* Maximum current per NAC: 1.25 amps (expandable to 2.5
amps).
*Maximum battery charging capability: 18 AH.
Auxiliary Outputs
* Resettable four-wire smoke detector power@ 500 mA.
*Non-resettable power @ 500 mA.
NOTE: Total current for auxiliary power outputs and two NACs
must not exceed 3.0 amps. .
*Integral Form-C Alarm, Trouble and Supervisory relays,
rated at: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30
VAC (resistive).